Natural gas cogen 60 Hz LowNOx

Reduce energy costs  -  avoid CO2 -  save resources

SCHMITT ENERTEC GmbH - Siemensstraße -  56743 Mendig  - Germany
Phone +49 2652/93518 10 - Fax. +49 2652/93518 22
  change to US-scales                                                                                              Download sheet as PDF
 Type Generator-power
[KW]
Thermal
Power
[KW]
Electric
efficiency
[%]
Intercooler-
temperature
[°K]
Cylinder number/
Arrangement
Weight
approx.
[t]
Dimensions
L x W x H
[m]

Heat extraction:
Heating water temperature: 90 °C outlet flow temp., max 70 °C return flow temp.
Special layout up to 120 °C outlet flow temperature upon request
Rating Conditions:
Combustion air/ambient temperature 27 °F; Altitude max. 300 m;  Methan number > 76:
Exhaust gas emissions:
 NOx < 50 ppm ; 0,15 Gms / Bhp -hr
 NOx < 1100 ppm; 0,6 Gms/ Bhp -hr  

 

All Data on this sheet is for information only  and not binding. Guaranteed are only the values in commercial 
 

Rich burn, naturally aspirated
FMB-62- GSK 62 88 34,1 - 4 / Reihe 2,4 2,8 x 0,85 x 1,85
FMB-80-GSK 80 124 34,3 - 6 / Reihe 2,6 2,8 x 0,85 x 1,85
MB-110- GSK 110 192 32,8 - 6 / Reihe 3,1 3,6 x 1,05 x 1,85
MB-135-GSK 135 233 33,3 - 6 / Reihe 3,2 3,6 x 1,05 x 2,05
MB-160-GSK 160 274 33,4 - 8 / V 90° 3,4 3,6 x 1,25 x 2,05
MB-240-GSK 240 423 33,4 - 12 / V 90° 4,3 3,6 x 1,25 x 2,05
Rich burn, turbocharged with emission gas return
FMB-215-GSM 195 315 34,3 50 6 / Reihe 3,6 3,6 x 1,25 x 2,45
FMB-230-GSMK 240 410 35,1 50 8 / V 90° 3,7 3,6 x 1,45 x 2,45
FMB-270-GSMK 370 624 35,1 50 8 / V 90° 5,6 3,6 x 1,45 x 2,45