ENERGIN® GEN+

Generator Sets with heat recovery

ENERGIN® GEN+

Our ENERGIN® GEN+ units are generators sets with heat recovery from engine jacket water, lube oil and first stage mixture cooling. As an option they can be equipped with an exhaust heat exchanger cooling the exhaust to 250°C. For more efficient heat recovery please refer to our CHP units. ENERGIN® GEN+ units are prepared for power production in island or parallel mode with other generators and/or the utility.

Basic features are:

  • Electric power range 115 – 500 kWe
  • Thermal power range 109 – 481 kWth
  • Up to 41,6 % electric efficiency
  •  Up to 83,0 % overall efficiency
  • Low noise option <70 dB(A)
  • Plug and play type
  • Fuel options: Natural gas, Biogas, Woodgas, LPG

        RSE_Download_05   Download Flyer: ENERGIN® GEN+ | 50 Hz

        RSE_Download_05   Download Flyer: ENERGIN® GEN+ | 60 Hz

50 Hz

Natural gas, 400 V, 50 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
M06 GEN+ G140M06-GT0D4114038,611169,2
M06 GEN+ G200M06-GTID4120041,013167,8
M06 GEN+ G250M06-GT2D4125041,812863,2
M08 GEN+ G260M08-GTID4126041,017368,3
M08 GEN+ G333M08-GT2D4133341,917463,8
M12 GEN+ G400M12-GTID4140041,126468,2
M12 GEN+ G500M12-GT2D4150042,125563,6

Biogas, 400 V, 50 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
M06 GEN+ B140M06-BT0D4114039,39866,8
M06 GEN+ B200M06-BTID4120041,812066,9
M06 GEN+ B250M06-BT2D4125042,612063,0
M08 GEN+ B260M08-BTID4126041,715967,2
M08 GEN+ B333M08-BT2D4133342,616263,3
M12 GEN+ B400M12-BTID4140041,924167,1
M12 GEN+ B500M12-BT2D4150042,724163,3

Woodgas, 400 V, 50 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
M06 GEN+ H122M06-HT2D4112234,810263,9
M08 GEN+ H166M08-HT2D4116634,914064,3
M12 GEN+ H250M12-HT2D4125035,020864,1

 

60 Hz

Natural gas, 60 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
GEN+ G150/60HzM06-GT0D4115037,012768,4
GEN+ G210/60HzM06-GTID4121039,514967,5
GEN+ G250/60HzM06-GT2D4125040,314563,7
GEN+ G280/60HzM08-GTID4128039,520067,7
GEN+ G333/60HzM08-GT2D4133340,419463,9
GEN+ G420/60HzM12-GTID4142039,630067,9
GEN+ G500/60HzM12-GT2D4150040,528563,6

Biogas, 60 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
GEN+ B150/60HzM06-BT0D4115037,811266,0
GEN+ B210/60HzM06-BTID4121040,213465,9
GEN+ B250/60HzM06-BT2D4125041,113062,5
GEN+ B280/60HzM08-BTID4128040,218066,1
GEN+ B333/60HzM08-BT2D4133341,217562,8
GEN+ B420/60HzM12-BTID4142040,427066,4
GEN+ B500/60HzM12-BT2D4150041,225862,5

Woodgas, 60 Hz

ENERGIN® typeEngine typeElectrical power / kWElectrical efficiency / %Thermal power / kWOverall efficiency / %
GEN+ H140/60HzM06-HT2D4114033,312563,0
GEN+ H180/60HzM08-HT2D4118033,416063,1
GEN+ H275/60HzM12-HT2D4127533,524963,8